Specifications of the ZARYA unit
Cylinder volume, gal: | 2.64 ±0.13 |
Operating pressure, at ambient temperature 20±2°С, Psi: | 232,06 |
Minimum operating pressure, Psi: | 145,04 |
Test pressure, Psi: | 797,71 |
Inside diameter of shut-off valve, in: |
0.7086 |
Response time delay (from the moment the starting impulse is applied) sec, not more: | 2 |
Discharge time at temperature 20±2°С, sec, not more: | 10 |
Membrane burst pressure , Psi: | 725±72.50 |
Rest of gas fire extinguishing agents after discharge | No |
Length of unit, in, not more 27.55 | 27,55 |
Quantity of actuations, times, not less |
10 |
Specifications of electric start-up of the unit
Actuating current, А | 0.7+0,1 |
Duration of voltage application, not lower | 0.05 |
Internal resistance, Ohm from | 2 to 4.5 |
Maximum current when checking circuit integrity (safe current) should not exceed | 0.05 А |
DC voltage, V | from 3.6 up to 24 |
Type of start up of unit
Automatic start
occurs by means of destroying the thermo bulb of the shut-off valve of the unit by an electromechanical inducer (one-shot device) when an electric triggering pulse is supplied from the fire control device;
Manual start
occurs by means of destroying the thermo bulb of the shut-off valve by an electromechanical inducer (one-shot device) when an electric triggering pulse is supplied from the starting device by pressing the button of the manual start.
Self-contained start:
occurs be means of destroying of the thermo bulb of the shut-off valve under the influence of an increase of ambient temperature above 154,4 °F.
Overal dimentions
Height, in: | 13.78 (15.35*) |
Weight (without gas fire extinguishing agents), lb, not more | 16.98(18.08*) |
Diameter, in: | 12.20 |
Maximum filling of unit with gas fire extinguishing agents
HFC-227ea | 24,25 lb |
FK-5-1-12 | 26,46 lb |
Specifications of fire extinguishing agents
Designation of gas fire extinguishing agents | Chemical designation (formula) of gas fire extinguishing agents | Symbolic designation |
HFC-227ea | Heptafluoropropane (CF3CHFCF3) | HFC-227ea |
FК-5-1-12 | Dodecafluoro-2- methylpentan-3-one CF3CF2C(O)CF(CF3)2 |
FK-5-1-12 |
Some of our products

ZARYA-22 with thermo bulb
Weight | Height | Diameter |
24.25(25.35*) lb | 19.88(21.46*) in | 14.17 in |

ZARYA-10 with solenoid valve
Weight | Height | Diameter |
22.71 lb | 15.55 in | 12.20 in |

ZARYA-3 with High pressure hose
Weight |
Height | Diameter |
13.01 lb | 13.90 in | 8.27 in |

ZARYA-10 with High pressure hose
Weigh |
Height | Diameter |
20.28 lb | 14.96 in | 12.20 in |